Various reports of vibrations from the telescope, typically altitude,
were reported during the last few months. Always the problem was
solved by changing something in the servo control loop, e.g.
disconnecting one or the other tachometers, cleaning the said tachos
and finally removing the new alt/az amplifiers. It is believed the
main cause of the problem was that the new amplifiers had a slightly
too high gain with respect to the old ones (1.62 against 1.5). All the
new amplifier gains have now been reduced to 1.47 and are ready
to be tested again.